Add To Cart
share
Sick LFT0600-01B0C40 Overview
FLUID LEVEL SENSOR
Sick LFT0600-01B0C40 Description
- Time-of-flight measurement technology
- Up to 4 switching outputs, combination of analog and digital outputs possible
- Small deadband, ideal for small containers
- Simple, single-button teach
- Flexible probe length up to 2,000 mm
- No re-calibration necessary when fluid properties change
- Measurement independent of installation conditions and tank material
- Filter available for dirty and contaminated fluids
- High resolution, accuracy, and repeatability
- Reliable measurement independent of liquid type, installation condition and tank material due to TDR technology
- One device performs the functionality for switching and continuous applications, reducing the number of sensors required
- Reduced installation time and costs through high flexibility
- No re-calibration necessary, saving commissioning time
- A variety of available probe lengths meets the needs of many applications
- No moving parts reduces maintenance costs
Your benefits
| Features | |
| Medium: | Fluids |
| Measurement: | switch, continuous |
| Measurement range: | 30 mm ... 590 mm |
| Probe length: | 600 mm |
| Process pressure: | 1 bar |
| Process temperature: | 0 C ... 80 C |
| WHG approval: | - |
| GOST approval: | ![]() |
| UL approval: | - |
| Performance | |
| Dielectricity constant: | >= 1,8 |
| Accuracy: | 3 mm |
| Repeatability: | < 2 mm |
| Resolution: | 1 mm |
| Mechanical data | |
| Housing material: | PBT |
| Process connection: | G 3/4 A |
| Wetted parts: | Stainless steel 1.4404 / 316L |
| Inactive area: | each 10 mm |
| Electrical data | |
| VDE protection class: | III |
| Supply voltage: | 18 V DC ... 30 V DC |
| Residual ripple: | <= 5 Vpp |
| Power consumption: | <= 90 mA at 24 V without output load |
| Initialization time: | 4 s |
| Output signal: | 2NO/ 2NC, PNP |
| Hysteresis: | 3 mm |
| Connection type: | M12x1, 8-pol |
| Response time: | 200 ms |
| Capacitive load: | 100 nF |
| Inductive load: | 1 H |
| Enclosure rating: | IP 67 |
| Ambient data | |
| Ambient temperature, operation: | -10 C ... 60 C |
| Ambient temperature, storage: | -40 C ... 80 C |
Contact Us