Add To Cart
share
Sick MZR2-0V3-N-AWO Overview
Magnetic cylinder sensor MZR2-03V-N-AW0 NAMUR
Sick MZR2-0V3-N-AWO Description
- Universal mounting with tension strap for cylinders with diameters of up to 100mm
- NAMUR as per EN 60 947-5-6
- Enclosure rating IP 67
- Sturdy aluminum housing
- TV 99 ATEX 1398 EX II 2 G Ex ia IIC T6 Ta: -20...70C
- LED function indicator
- Highly resistant to shock and vibrations
- High switching point accuracy
Your benefits
| Features | |
| Switching frequency: | 5,000 Hz |
| Connection type: | Cable, 2-wire, 2 m |
| Switching output: | NAMUR |
| Electrical wiring: | DC 2-wire |
| Sensing face: | Front |
| According to EN60529 | |
| Mechanics/electronics | |
| Enclosure rating: | IP 67 |
| Cylinder types with adapter: | Roundbody cylinder |
| Housing length: | 30 mm |
| Supply voltage: | 5 V DC ... 25 V DC |
| Residual ripple: | ≤ 5 % 1) |
| Voltage drop: | ≤ 1.5 V 2) |
| Continuous current Ia: | ≤ 300 mA |
| Repeatability: | ≤ 0.1 mm 3) |
| EMC: | Nach EN 60947-5-6 |
| Cable material: | PVC |
| Conductor cross-section: | 0.34 mm2 |
| Short-circuit protection: | ![]() |
| Housing material: | Metal |
| Sensing area material: | Plastic |
| Time delay before availability: | ≤ 2 ms |
| Ambient temperature, operation: | -25 C ... 70 C |
| Shock/vibration stress: | 30 g, 11 ms/10 ... 55 Hz, 1 mm |
| Response sensitivity: | ≤ 3 mT |
| Hazardous area category: | 2G |
| Temperature drift (of sr):: | 0.005 mm/C |
| Power consumption, attenuated: | ≥ 2.5 mA |
| Power consumption, unattenuated: | ≤ 1 mA |
| Input voltage Ui max: | 16 V 4) |
| Input power Pimax.: | 100 mW 5) |
| Input current Ii max: | 30 mA for connection to a sperately certified intrinsically safe circuit only |
| Internal capacitance Ci max.: | 15 nF 6) |
| Internalinductance Li max.: | ≤ 35 H 7) |
| Nominal voltage: | 8.2 V DC |
| Cable resistance: | ≤ 50 Ω |
| EC type approval certificate: | TV 99 ATEX 1398 |
| Ex marking (ATEX): | EXII 2 GEx ia IIC T6 Ta: -20...70C |
| 1) 3) 2) At Ia max 4) 5) 6) 7) For connection to a sperately certified intrinsically safe circuit only | |