Sick UE4155 Overview
UE 4155 8 field-signal connections; 2 SDL connections; incl. CDS Software; suitable for function packages for CDS
Sick UE4155 Description
- Remote module up to enclosure rating IP 67
- Support for PROFIBUS-DP V1: cyclic communication with DP-Master Class 1 (central control), acyclic communication with DP-Master Class 2 (configuration and diagnostic tool)
- Support for PROFIsafe V2.0
- Two SDL connections for easy integration of intelligent SICK safety sensors
- Simple configuration and diagnostics using the CDS (Configuration & Diagnostic Software)
- Reduced implementation costs using safety automation devices without a control cabinet
- Fast integration of safety solutions into a safety PLC, or into a wide PROFIBUS PROFIsafe fieldbus
- Allows use of extended functionality of SICK safety sensors in an easy to use fashion
- Comprehensive diagnostics provide fast troubleshooting, which reduces downtime
Your benefits
| Applications | |
| Safety command devices: | ![]() |
| Electro-mechanical safety switches: | ![]() |
| Non-contact safety switches: | ![]() |
| Opto-electronic protective devices: | ![]() |
| Two-hand control systems: | ![]() |
| Operating mode selector switch: | ![]() |
| Muting sensors: | ![]() |
| Muting lamp: | ![]() |
| Functions | |
| Safedevice communication via EFI/SDL: | ![]() |
| Reset/restart: | Manual / automatic / configurable |
| Technical data | |
| Fieldbus: | PROFIBUS PROFIsafe |
| Enclosure rating: | IP 67 |
| Ambient operating temperature from ... to: | 0 C ... 55 C |
| Protection class: | III |
| Weight: | 620 g |
| Safety integrity level: | SIL3 (IEC 61508) |
| Category: | Category 4 (EN ISO 13849) |
| Performance level: | PL e (EN ISO 13849) |
| PFHd: | 1.33 * 1E-09 |
| TM (Mission Time): | 20 a |
| Supply voltage: | 19.2 V DC, 24 V DC, 28.8 V DC |
| Maximum power consumption: | ≤ 9 A |
| Number of safety inputs: | 8 dual-channelor 16 single-channel |
| Input voltage HIGH field signal inputs: | 11 V, 24 V, 28.8 V |
| Input delay field signal inputs: | Configurable 0 ... 90 ms |
| Number of test/signal outputs (with current monitoring): | ≤ 16 (2) |
| Number of SDL connections: | 2 |
| Output voltage HIGH field signal outputs: | UV, without load, switched-on |
| Output current field signal output: | 0 mA ... 700 mA |
| Minimum current for fault monitoring: | 7 mA ... 40 mA, on field-signal connections 7 and 8 1) |
| Maximum current SDL connections: | 1.4 A |
| Maximum internal resistance SDL connections (power supply): | 0.3 Ω |
| Input voltage HIGH SDL connections (OSSD inputs): | 13 V, 24 V, 28.8 V |
| Maximum test puls rate SDL connections (OSSD inputs): | 500 Hz |
| Maximum test pulse width SDL connections (OSSD inputs): | 700 s |
| Baud rate PROFIBUS connection: | 9.6 kbit/s ... 12 Mbit/s |
| Address range PROFIBUS connection: | 3 ... 125 |
| Ident numberPROFIBUS: | 071A hex |
| 1) Only when the connection is configured as an output for a muting lamp. | |