Sick UE4215-04CA200 ASI Overview
UE4215 AS-i Safety at Work bus connection for AOPD
Sick UE4215-04CA200 ASI Description
- Connection of electrosensitive protective equipment (ESPE) with self-monitoring semiconductor outputs (OSSDs)
- Connection for the sender/receiver unit of an electrosensitive protective system
- AS-Interface (yellow AS-Interface cable)
- External voltage supply for ESPE via 24 V ribbon cable (black AS-Interface cable)
- AS-Interface version 2.1
- Remote module up to enclosure rating IP 67
- Allows the realization of distributed machines and systems via an expandable and remote concept
- Reduction of setup costs by using devices for safety automation without a control cabinet by using AS-Interface technology
Your benefits
Applications | |
Safety command devices: | - |
Electro-mechanical safety switches: | - |
Opto-electronic protective devices: | ![]() |
Functions | |
Safedevice communication via EFI/SDL: | - |
Reset/restart: | Manual / automatic / configurable |
Technical data | |
Fieldbus: | AS-Interface Safety at Work |
Enclosure rating: | IP 67 (EN 60529) |
Ambient operating temperature from ... to: | -25 C ... 70 C |
Protection class: | III |
Weight: | 100 g |
Safety integrity level: | SIL3 (IEC 61508) |
Category: | Category 4 (EN ISO 13849) |
Performance level: | PL e (EN ISO 13849) |
PFHd: | 9.0* 1E-09 |
TM (Mission Time): | 20 a |
Maximum power consumption: | ≤ 60 mA |
Number of safety inputs: | 1 dual-channel |
OSSD input voltage HIGH: | 13.5 V, 24 V, 28.8 V |
OSSD input test pulses: | 0 Hz ... 25 Hz |
OSSD input test pulse width: | 0 s ... 550 s |
AS-Interface profile: | S-O.B.E |
AS-Interfaceversion: | 2.1 |
Data bits IN input channel I1: | AS-Interface Safety at Work code sequence on D0, D1 |
Data bits IN input channel I2: | AS-Interface Safety at Work code sequence on D2, D3 |
Data bits OUT LED alarm: | not used |
AS-interface voltage range: | 26.5 V DC ... 31.6 V DC |
Supply voltage AUX PWR: | 16.8 V, 24 V, 28.8 V |
Minimum opening time for the contacts socket I1/2: | 51 ms |
Output current Pin 1 (AUX L+): | 1.4 A |
Cable capacitance socket I1/2: | 100 pF |
Maximum response time: | 22 ms |
ESPE sender total output current (AUX L+): | 1.4 A |