Add To Cart
share
Sick UE4470 SAFETY NETWORK CONTROLLER Overview
UE4470-22EE690 Safety Network Controller - 16 single channel safety capable inputs (up to 8 dual channel) - 4 test/signal outputs - 8 single channel safety capable outputs(up to 4 dual channel); semiconductor type
Sick UE4470 SAFETY NETWORK CONTROLLER Description
- Network-compatible safety controller with a wide range of certified function blocks
- Evaluates and logically links local or remotely connected safety sensors and actuators
- Flexibly expandable with remote I/O units in IP 20 or IP 67
- 16 safety inputs / 8 safety outputs
- Remote configuration of other DeviceNet Safety devices via the network
- Freely configurable and flexible safety automation software allows the conversion of both easy and complex tasks, providing increased user flexibility
- Modular expandability and remote I/O reduce costs and provide maximum network flexibility
- Predefined functions ensure fast implementation of the application, e.g., different muting variants or functions that provide complete press protection
Your benefits
| Applications | |
| Safety command devices: | ![]() |
| Electro-mechanical safety switches: | ![]() |
| Non-contact safety switches: | ![]() |
| Opto-electronic protective devices: | ![]() |
| Two-hand control systems: | ![]() |
| Operating mode selector switch: | ![]() |
| Muting sensors: | ![]() |
| Muting lamp: | ![]() |
| Functions | |
| Safedevice communication via EFI/SDL: | - |
| External device monitoring: | ![]() |
| Reset/restart: | Manual / automatic / configurable |
| Logical functions: | AND, NOT, OR, XNOR, XOR |
| On-delay: | ![]() |
| Off-delay: | ![]() |
| Door monitoring: | ![]() |
| Signal routing: | ![]() |
| Technical data | |
| Fieldbus: | DeviceNet Safety |
| Enclosure rating: | IP 20 |
| Ambient operating temperature from ... to: | -10 C ... 55 C |
| Protection class: | III (EN 61140) |
| Weight: | 460 g |
| Safety integrity level: | SIL3 (IEC 61508) |
| Category: | Category 4 (EN ISO 13849) |
| Performance level: | PL e (EN ISO 13849) |
| PFHd: | 4.2 * 1E-10 |
| TM (Mission Time): | 20 a |
| Supply voltage: | 20.4 V DC, 26.4 V DC |
| Maximum power consumption: | ≤ 4 mA |
| Connection type supply voltage: | Spring terminal plug |
| Number of safety inputs: | 8 dual-channelor 16 single-channel |
| Input voltage HIGH field signal inputs: | 11 V DC, 30 V DC |
| Input delay field signal inputs: | Configurable 0 ... 126 ms |
| Number of test/signal outputs (with current monitoring): | 4 (0) |
| Type of output test/signal outputs: | PNP semiconductor |
| Output current test/signal outputs: | 700 mA |
| Number of safe outputs: | 4 dual-channelor 8 single-channel |
| Type of output safety capable outputs: | current sourcing(PNP) |
| Maximum switching current safety capable outputs: | 500 mA |
| Maximum number originator connections: | 16 |
| Maximum number of safety target connections: | 4 |
| DeviceNet communication rate: | 125 kbit/s, 250 kbit/s, 500 kbit/s, Autobaud detection |
| Connection type DeviceNet: | Spring terminal block |
Contact Us