Add To Cart
share
TM
Patented TEMA (time extended measurement algorithm) self-calibration software
10K Temperature sensor
Sample Method: Diffusion
Measurement range Analog Output: 0–2000 ppm factory default adjustable to 10,000 ppm
Sensor tolerance Accuracy:
Typical Conditions: °60° to 90°F (15° to 32°C)
0–2000 ppm: ± 110 ppm
Annual drift ± 10 ppm (negligible) with TEMA on
± 20 ppm typical with TEMA off
Response Time: 0–90% FS < 2 minutes
Warm-Up Time: 25 C < 2 minutes
Operating Conditions: 32° to 122°F (0° to 50°C)
0–95% RH (relative humidity), non-condensing
Storage Conditions: –4° to 158°F (–20° to 70°C)
Power 18-30 Vac RMS, 50/60 Hz - half wave rectified (dedicated)
18-42 Vdc polarity protected (dedicated)
1.75 Va maximum average power
2.75 Va peak power