4A48-96 AC current / voltage configurable indicators
FEATURE
AC voltage, AC current direct input on instrument terminals
Protected by a personal code
Configurable by serial link
Labels to customize measured physical unit
DESCRIPTION
Microprocessor based indicator in both 48x48 (1/16 DIN) and 96x48 (1/8 DIN) formats manufactured with SMT.
The instruments have a lexan membrane faceplate (guaranteed to IP65) which has 3 keys, a 3-digit display for the 48x48 format or a 3 / 4 digit display for the 96x48 format.
The input signal section provides for the visualisation of the sinusoidal effective value corresponding to following signals:
AC voltage: 0 to 2, 0 to 20, 0 to 200 and 0 to 500Vac
AC current: 0 to 20, 0 to 50, 0 to 200mAac 0 to 1, 0 to 5Aac
The selection is made using the faceplate keys and correct input terminals.
No external shunt or adapter is required.
The programming of the instrument is made easy by grouping the parameters in function blocks and by a simplified data entry menu.
The configuration can be simplified even further using the PC programming kit made up of a connection cable and a menu guide program that runs under Windows (see data sheet cod. 80021).
A configurable personal software protection code (password protection) can be used to restrict the levels of editing and displaying the configuration parameters.
4T72 Temperature indicator with configurable input
FEATURE:
1) Faceplate configurable input
2) Protected by a personal code
3) Configurable by a serial link
4) Transmitter power supply incorporated
5) Custom thermocouple linearisation available
6) Internal linearisation for engineering units
7) Labels provided for the most common physical units
Microprocessor based indicator in 72x36 format manufactured with SMT.
The instruments have a lexan membrane faceplate (guaranteed to IP65) which has 3 keys, a 2, 3 / 4-digit display.
The input signal can be selected from a wide range of sensors:
Thermocouples of type J, K, R, S, T, B, E, N, L GOST, U, G, D, C
Resistance thermometers Pt100, Pt100J (japanese standard) 2 / 3 wire
PTC and NTC themistors
Linear inputs 0 to 60/12 to 60mV, 0 to 20/4 to 20mA, 0 to 10/2 to 10/0 to 5/1 to 5/0 to 1/0, 2 to1V
The selection is made using the faceplate keys and correct input contact.
No external shunt or adapter is required.
The programming of the instrument is made easy by grouping the parameters in function blocks and by a simplified data entry menu.
The configuration can be simplified even further using the PC programming kit made up of a connection cable and a menu guide program that runs win windows (see data sheet cod. 80021).
A configurable personal software protection code (password protection) can be used to restrict the levels of editing and displaying the configuration parameters.